top of page

Model

900368

Application recommend

L-N

TYPE

1+2

kA

25kA

Up

1.5 kV

Specification

DEHNvap

DVA CSP 1P 255 FM (900 368)

■ Prewired combined lightning current and surge arrester, energy-coordinated with power supply systems for cell sites (DEHNvap CSP ... CellSite Protection)

■ Maximum system availability due to follow current limiting RADAX Flow spark gap technology

■ Easy replacement of protection modules without tools due to module release button

Single-pole modular combined lightning current and surge arrester with high follow current limitation; with remote signalling contact for monitoring device (floating changeover contact).

  • SPD according to EN 61643-11 / ... IEC 61643-11 type 1 + type 2 / class I + class II

  • Energy coordination with terminal equipment (≤ 5m) type 1 + type 2 + type 3 

  • Nominal voltage (a.c.) (UN) 230 V (50 / 60 Hz) 

  • Max. continuous operating voltage (a.c.) (UC) 264 V (50 / 60 Hz) 

  • Lightning impulse current (10/350 µs) (Iimp) 25 kA

  • Specific energy (W/R) 156.25 kJ/Ohm kJ/Ohm

  • Nominal discharge current (8/20 µs) (In) 25 / 100 kA

  • Voltage protection level [L-N]/[N-PE] (UP) ≤ 1.5 kV

  • Follow current extinguishing capability (Ifi) 25 kAeff

  • Follow current limitation/Selectivity no tripping of a 20 A gG fuse up to 25 kArms (prosp.) 

  • Response time (tA) ≤ 100 ns

  • Max. backup fuse 315 A gG

  • Max. backup fuse (L-L') 125 A gG

  • Temporary overvoltage (TOV) (UT) - characteristic 440 V / 120 min. – withstand

  • Operating temperature range (parallel connection) (TUP) -40°C...+80°C 

  • Operating temperature range (through-wiring) (TUS) -40°C...+60°C 

  • Operating state/fault indication green / red 

  • Number of ports 1 

  • Cross-sectional area (L/N, L'/N', N/PE(N)) (min.) 10 sq-mm. solid / flexible 

  • Cross-sectional area (L/N, N/PE(N)) (max.) 50 sq-mm. stranded / 35 sq-mm. flexible 

  • Cross-sectional area (L'/N') (max.) 35 sq-mm. stranded / 25 sq-mm. flexible 

  • For mounting on 35 mm. DIN rails acc. to EN 60715 

  • Enclosure material thermoplastic, red, UL 94 V-0 

  • Place of installation indoor installation 

  • Degree of protection IP 20 

  • Capacity 2 module(s), DIN 43880

  • Approvals KEMA 

  • Type of remote signalling contact changeover contact 

  • Switching capacity (a.c.) 250 V / 0.5 A 

  • Switching capacity (d.c.) 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A 

  • Cross-sectional area for remote signalling terminals max. 1.5 sq-mm solid / flexible 


1.5 kV